QUALITY OPEN & SILENT
CUMMINS GENERATORS
UNBEATABLE PRICES
Contact us

 

CUMMINS/NEWAGE PRICE LIST

British Made Generators using Cummins Engines coupled to Newage Alternators. Prices in UK Sterling Pounds (GBP)

New Generators - British Made New Generators - Perkins New Generators - Newage UCC
Click here to open the
XE.com Currency Converter
50Hz @ 1500 RPM (400 / 230 volt)
All KVA RATINGS ARE CONTINUOUS (PRIME)
KVA ENG TYPE OPEN SETS Additional Cost for Fuel
Consumption
Litre/Hr
Manual
Start
Auto
Start
ATS
Panel
Acoustic
Enclosure
CE
CERT
(EU Only)
106 6BT5.9G6 8913,3 9366,5 720,5 - 154 23.8
135 6BTA5.9G3 10842,7 11338,8 742,5 3205,4 154 32
180 6CTA8.3G2 14346,2 14710,3 927,3 4154,7 154 42
200 6CTAA8.3G3 15923,6 16287,7 1018,6 4139,3 154 42.7
225 QSL9G2 19221,4 19648,2 1284,8 P.O.A. 154 47
250 QSL9G3 20307,1 20781,2 1383,8 P.O.A. 154 53.3
315 NT855G6 22259,6 22613,8 1633,5 P.O.A. 184,8 56.7
355 NTA855G4 25174,6 25602,5 1633,5 P.O.A. 184,8 68.2
500 QSX15G8 35866,6 36506,8 3206,5 P.O.A. 184,8 102
635 VTA28G5 44940,5 44209 4262,5 P.O.A. 243,1 121
800 QSK23G3 59536,4 587301 4717,9 P.O.A. 297 159
27°C (80°f) 152M (500ft) @ 60% relative humidity
All prices are in Sterling Pounds GBP Ex works UK
Prices are subject to VAT @17.5% (where applicable)

 

 

Standard Tempest Specification

Cummins B & C Range ( 106 to 200 KVA )

New Generators - British Made New Generators - Perkins  
Generating Set
  • Set Mounted Tropical Duty Radiator
  • Engine Driven Cooling Fan with Protection Guard
  • Radiator Stone Guard
  • Fuel, Lubricating Oil and Air Filter with Restriction Indicator
  • Mechanical governing at 1500/1800 RPM in accordance with BS5514A1 (1)
  • 12 Volt electric start with charging alternator (2)
  • Protection Switches for
    • High Engine Temprature
    • Low oil pressure
    • Low Coolant Level ( C Series Only )
  • Wiring to Control Panel
  • Steel base frame with integral 8 hour capacity fuel tank, complete with contents gauge, steel wire braded fuel lines, fill, vent and drain fittings
  • Anti vibration mountings fitted between the engine/alternator feet and base
  • Set mounted Yuasa maintenance free lead acid battery with leads and terminals
  • Exhaust flexible section with connections
  • S.L.S. Silencer supplied loose
  • Load and function tests
  • Paint finish to our standard scheme
  • Comprehensive user manual
Keystart

Alternator mounted profile control panel comprising -

  • Ammeter per phase
  • 1 x voltmeter
  • Voltmeter selector switch
  • Dual scale frequency/RPM indicator
  • Hour counter
  • 3 pole MCB/MCCB Mounted in control panel (3)
  • Deep Sea 701 keystart module
  • Shutdown indicator for
    • High Engine Temperature
    • Low oil pressure
    • Overspeed
    • Low Coolant Level (4)
  • Oil Pressure Gauge
  • Water temperature gauge
  • Battery voltmeter
Autostart

As keystart but comprising the following additions -

  • Constant Potential barrety charger
  • Battery charger On/Off pushbutton
  • Deep Sea 521K autostart module in place of 701 module
  • Off/Auto/Manual selector keyswitch
  • Indicators for
    • Power On
    • Remote start present
    • Charge Fail
    • Common Alarm
    • Fail to start
  • Multi attempt to start programme
  • Programmed timers for
    • Delay on start
    • Mains restoration
    • Run on for engine cooling
    • Crank period
    • Protected Override
ATS

Wall mounted enclosure comprising -

  • 4 Pole changeover contactors
  • Indicators for
    • Mains available
    • Mains on load
    • Generator Available
    • Generator on load
  • Phase failure monitor

(1) The 6BTA5.9G3 & 6CTAA8.3G3 are fitted with electronic governing as standard.

(2) C Series Engines are fitted with 24 V electrics.

(3) Above 250 Amp, the MCCB is supplied fitted in an alternator mounted enclosure separate to the autostart control panel.

(4) C Series Only

 

Cummins UK

Cummins UK

 

Standard Tempest Specification

Cummins K50, QSK45 & 60 Range ( 200 to 800 KVA )

New Generators - British Made New Generators - Perkins  
Generating Set
  • Set Mounted Tropical Duty Radiator
  • Engine Driven Cooling Fan with Protection Guard
  • Radiator Stone Guard
  • Fuel, Lubricating Oil and Air Filter(s) with Restriction Indicator(s)
  • Electronic governing at 1500/1800 RPM in accordance with BS5514A1 (1)
  • 24 Volt electric start with charging alternator
  • Protection Switches for
    • Low oil pressure
    • High Engine Temprature
    • Low coolant level
  • Wiring to Control Panel
  • Open channel baseframe
  • Steel wire braded fuel lines terminated to baseframe
  • Anti vibration mountings fitted between the engine/alternator feet and base (3)
  • Set mounted Yuasa maintenance free lead acid battery with leads and terminals
  • Exhaust flexible section(s) with connections
  • S.L.S. exhaust Silencer(s) supplied loose
  • Load and function tests
  • Paint finish to our standard scheme
  • Comprehensive user manual
Keystart (Upto 1600 A)

Alternator mounted profile control panel comprising -

  • Ammeter per phase
  • 1 x voltmeter
  • Voltmeter selector switch
  • Dual scale frequency/RPM indicator
  • Hour counter
  • 3 pole MCB/MCCB in separate alternator mounted cubicle
  • Deep Sea 701 keystart module (1)
  • Shutdown indicator for
    • High Engine Temperature
    • Low oil pressure
    • Low coolant level
    • Overspeed
  • Oil Pressure Gauge
  • Water temperature gauge
  • Battery voltmeter
Keystart (Above 1600 A)

As above but with ACB mounted in a separate freestanding cubicle

Autostart (Without MCCB)

As keystart but comprising the following additions -

  • Constant Potential barrety charger
  • Battery charger On/Off pushbutton
  • Deep Sea 521K autostart module in place of 501K module
  • Off/Auto/Manual selector keyswitch
  • Indicators for
    • Power On
    • Remote start present
    • Charge Fail
    • Common Alarm
    • Fail to start
  • Multi attempt to start programme
  • Programmed timers for
    • Delay on start
    • Mains restoration
    • Run on for engine cooling
    • Crank period
    • Protected Override
  • Excluding MCCB
ATS

Wall mounted enclosure comprising -

  • Motor operated MCCB's 1000 A to 1250 A
  • Motor operated ACB's 1600 A and above
  • Indicators for
    • Mains available
    • Mains on load
    • Generator Available
    • Generator on load
  • Phase failure monitor

(1) QSK 45 & 60 have electronic management

Keystart control panels fitted to sets with engine management system have individual indicators and key start/stop switch in place of 701 module

(3) Anti vibration mountings are supplied loose on QSK & K50 models

Amps are at PRP Rating