TOP QUALITY SUPER SILENT GAS GENERATORS
Natural gas, biogas and LPG

 

Contact us

 

GAS GENERATOR

2 or more sets can be synchronized to give power

Biogas CHP units
CHP Type   FMB-100-BSM FMB-125-BSM FMB-200-BSM FMB-230-BSM FMB-255-BSM FMB-285-BSM FMB-375-BSM FMB-430-BSM
Power kW 81 101 160 185 200 233 300 350
Electric Efficiency % 31,6 32,6 35,5 36,7 35,2 36,9 35,7 38,1
Thermal Power kW 135 164 223 215 273 262 439 371
Gas consumption (LHV) kW 256 310 451 504 569 632 841 918
Aspiration   natural turbo            
Intercooler configuration /water temperature   - - Intern / 80°C Extern / 50°C Intern / 80°C Extern / 50°C Intern / 80°C Extern / 50°C
No. of cylinder/configuration   6 / in line 8 / V 90 ° 6 / in line 6 / in line 8 / V 90 ° 8 / V 90 ° 12 / V 90 ° 12 / V 90 °
Bore / stroke mm 128 / 155 130 / 142 128 /155 128 /155 130 / 142 130 / 142 130 / 142 130 / 142
Displacement l 12 15,1 12 12 15,1 15,1 22,6 22,6
Weight approx. kg 3.200 3.400 3.500 3.500 3.600 3.600 5.400 5.400
Dimensions, approx. L x W x H 3,6 x 1,05 x 2,05 (m) 3,6 x 1,25 x 2,05 (m) 3,6 x 1,25 x 2,45 (m) 3,6 x 1,25 x 2,45 (m) 3,6 x 1,45 x 2,45 (m) 3,6 x 1,45 x 2,45 (m) 4,0 x 1,45 x 2,45 (m) 4,0 x 1,45 x 2,45 (m)
Exhaust gas emissions   To German law (TA - Luft 2002)              
Prices ex works
CHP unit EUR
114.285
121.386
134.546
138.645
160.149
163.789
179.721
188.361
Gas blower, loose supply EUR
5.980
5.980
7.025
7.025
7.025
7.025
7.025
7.025
Secondary exhaust silencer EUR
1.178
1.582
2.265
2.265
2.265
2.265
3.332
3.332
Dump radiator for jacket and exhaust heat, in loose supply , including control valve mounted on the unit maximum ambient Temperature 35 °C Sound pressure level < 60 dB(A) in 10 mtr. EUR
3.831
3.831
5.220
5.220
5.780
5.780
7.460
7.460
Flexible Connectors for Exhaust, jacket water and fuel gas EUR
780
780
837
837
891
891
891
891
Adder for Container version EUR
22.783
22.783
24.262
24.810
25.379
24.831
26.564
27.113
 
CHP Type   FMB-100-BSM FMB-125-BSM FMB-200-BSM FMB-230-BSM FMB-255-BSM FMB-285-BSM FMB-375-BSM FMB-430-BSM
Process water supply header with 3 EUR
7.184
7.184
7.184
7.184
7.622
7.622
7.622
7.622
Connections with shut-off valves, circulation  
Pump, loose supply  
2. Gas train for Propane EUR
2.177
2.177
2.177
2.177
2.177
2.177
2.177
2.177
Layout for emergency operation with control EUR
2.025
Function for a mains CB supplied by others  

 

Natural Gas CHP units
CHP Type   FMB-155-GSK FMB-190-GSK FMB-215-GSMK FMB-230-GSMK FMB-270-GSMK FMB-285-GSMK FMB-410-GSMK FMB-430-GSMK
Electric Power kW 122 151 173 185 220 233 334 350
Electric Efficiency % 34,3 35,2 35 35,7 36,5 36,9 36,4 37,3
Thermal Power kW 201 237 270 244 339 290 497 422
Gas consumption (LHV) kW 356 429 494 520 624 632 934 937
Aspiration   natural turbo            
Intercooler configuration /water temperature   - - Intern / 70°C Extern / 50°C Intern / 70°C Extern / 50°C Intern / 70°C Extern / 50°C
No. of cylinders/configuration   6 / in line 8 / V 90 ° 6 / in line 6 / in line 8 / V 90 ° 8 / V 90 ° 12 / V 90 ° 12 / V 90 °
Bore / stroke mm 128 /155 130 / 142 128 /155 128 /155 130 / 142 130 / 142 130/ 142 130/ 142
Displacement l 12 15,1 12 12 15,1 15,1 22,6 22,6
Weight approx. kg 3,200 3,400 3,500 3,500 3,600 3,600 5,400 5,400
Dimensions, approx. L x W x H 3,6 x 1,05 x 2,05 (m) 3,6 x 1,25 x 2,05 (m) 3,6 x 1,25 x 2,45 (m) 3,6 x 1,25 x 2,45 (m) 3,6 x 1,45 x 2,45 (m) 3,6 x 1,45 x 2,45 (m) 4,0 x 1,45 x 2,45 (m) 4,0 x 1,45 x 2,45 (m)
Exhaust gas treatment   3-Way Cat Oxi-Cat            
Exhaust gas emissions   To German law (TA -; Luft 2002)              
Prices ex works
CHP unit EUR
118.288
125.792
136.136
141.234
161.570
166.568
179.748
188.159
Heating water pump set with return lifting EUR
2.232
2.232
2.232
2.232
2.232
2.232
2.690
2.690
Layout for emergency operation with control function for a mains CB supplied by others EUR
2.025
Secondary exhaust silencer EUR
1.178
1.582
2.265
2.265
2.265
2.265
3.332
3.332
 
CHP Type   FMB-155-GSK FMB-190-GSK FMB-215-GSMK FMB-230-GSMK FMB-270-GSMK FMB-285-GSMK FMB-410-GSMK FMB-430-GSMK
Dump radiator for jacket and exhaust heat EUR
3.801
3.801
4.034
4.034
4.322
4.322
5.833
5.833

 

All prices in EURO, net, VAT to be added, ex works ;
Reference conditions: Ambient air/ combustion air 27 °C; erection altitude max. 300 m
Methane number >80
Scope of Supply
Natural Gas engine with synchronous generator connected with flexible coupling
Turbocharged lean burn engines with oxidation catalyst or
Natural aspirated rich burn engines with 3-way catalyst to achieve exhaust emissions according to German Law (TA Luft 2002)
Heat exchangers for Jacket water, lube oil, and exhaust, ready piped and insulated
Turbocharged engines with internal or external intercooler (External intercooler in loose supply to be mounted outside the building and piped by others
Electrical circulation pump for jacket water with electrical temperature control valve
Stainless steel critical exhaust silencer
Vibration isolators between engine/generator and baseframe as well as between baseframe and foundation
Gas train with dual solenoid valve, zero pressure regulator
Low fuel pressure system (25-100 mbar)
sound attentuating enclosure, 70 dB(A) in 1 mtr distance, with ventilating fan
PLC control for automatic operation in grid parallel mode
Utility grade protective relay
Phone modem for remote access and diagnostics by our service
Electrically operated power circuit breaker
24V lead acid battery, 20A battery charger
Lube oil make up system with 100 l storage tank, unit mounted
Validity until June 30, 2006